The interface device is designed for use in 24 V DC circuits. In addition to the switching function, the device is equipped with an additional electronic fuse protection function. In the event of an overload or short circuit in the power circuit, the device switches off quickly and automatically. The tripping current can be adjusted using DIP switches on the side. The housing form factor is identical to the PLC-INTERFACE product range. The overall width is 6.2 mm.
Thanks to the appropriate arrangement of the connections and the use of the PLC insertion bridges, it is possible to implement variable channel or block fuse protection in combination with relay or optocoupler plates. Existing PLC accessories (bridges, marking, V8 system cabling adapters, etc.) can be reused.
Features
Tripping current can be adjusted from 1 A ... 6 A in increments of 1 A via DIP switches
The interface block with fuse function is a built-in device
The contacts can also be used for normal switching functions